Foretec Electric
Janitza Solution Partner Blue

FLIT — Fault Loop Impedance Calculator

Design, verification and test reporting to IS 732:2019 · IS 3043:2018 · CEA (Safety) Regulations 2023 · NEC of India 2023 · IEC 60898-1/-2, IEC 60947-2, IEC 60269-1, IEC 60909-0, IEC 60287-1-1, IEC 61557-3

1 Project, Client & Test Details

2 System, Earthing Arrangement & Source

Earthing system and reference voltage

Cl. 4.2.11.4 / .5 / .6 of IS 732

Source — transformer or generator

%Z × kV² / (100 × MVA) — Eq. 7, IEC 60909-0
Splits Z into R and X for vector summation

3 Fault Loop — Circuit Levels (source → final circuit)

How to use. Add one level for each protective device in the loop, in order, starting at the main LV panel. Each level carries its own OCPD, line conductor and protective (PE) conductor. Impedances accumulate down the cascade exactly as in the fault loop. Enter measured values in section 4 once the installation is tested.

4 Measured Values & Instrument Accuracy (IEC 61557-3)

Total operating uncertainty of a loop-impedance meter shall not exceed ±30 % of the measured (fiducial) value — IEC 61557-3 with IEC 61557-1 Table 1. Enter the meter data sheet figures once; they apply to every measurement below.

5 Results & Compliance Summary

Fault loop impedance build-up

Prerequisite compliance at each level

Recommendations

6 Client Report

Use your browser's Print → Save as PDF. Set margins to Default and enable Background graphics so the section headers and logos print.

7 Reference Data & Basis of Calculation

Expressions used
Eq.ExpressionSource
1Z ≤ U0 / IaCl. 4.2.11.4.4, IS 732:2019
1ARA × IΔn ≤ 50 VCl. 4.2.11.5.3, IS 732:2019
2Zmax, allowable = ⅔ × ZCl. 6.2.3.6.2, Annex MM, IS 732:2019 — allowance for conductor temperature rise during the fault
3Zsource = %Z × kV² / (100 × MVA)Eq. 7, IEC 60909-0
4R = ρ × L / A ; Rac ≈ 1.1 RdcTable 1, IEC 60287-1-1:2023
5X = 2πf × 2×10−7 × [¼ + ln(D/r)] Ω/mIEC 60909-4 — self + external inductance
6Ib ≤ In ≤ Iz and I2 ≤ 1.45 IzCl. 4.4.4.1, IS 732:2019
7u = b(ρL/S·cosø + λL·sinø) Ib ; Δu% = 100u/U0Annex Y, IS 732:2019
8Smin = √(I²t) / k, for t ≤ 5 sCl. 4.4.5.5 and Cl. 5.4.3.1.2, IS 732:2019 (k from Table 11 and Annex EE Tables 58 to 62)
8ASp ≥ S for S ≤ 16 ; 16 for 16 < S ≤ 35 ; by calculation for S > 35Table 12, Cl. 17.2.2.2, IS 3043:2018
8BSeparate PE ≥ 2.5 mm² with mechanical protection, ≥ 4 mm² withoutCl. 17.2.2.3, IS 3043:2018
7Bρθ = ρ20 [1 + α20(θ − 20)]Table 1, IEC 60287-1-1:2023 — temperature correction of conductor resistivity
9B% = ±(B / fiducial value) × 100 ≤ 30 %IEC 61557-3 with Table 1 of IEC 61557-1
Table 1 IS 732 — maximum disconnection times
Conductor resistance and reactance (IS 8130 / manufacturer data)
OCPD trip multiples — IEC 60898-1 / -2, IEC 60269-1, IEC 60947-2
k values — Table 11 and Annex EE Tables 58 to 62 of IS 732
Protective conductor sizing — Table 12 and Cl. 17.2.2.3 of IS 3043
Transformer minimum %Z — Table 1 of IEC 60076-5
Cable current ratings — Tables 20 and 21 of IS 732
Line inductance — derivation behind Expression 5
Engineering notes, assumptions and deviations from the source workbook
Foretec Electric India Pvt Ltd — Passion in Power Quality · Authorised Janitza Electronics GmbH Blue-Level Solution Partner
This tool assists the designer and the tester. It does not replace the judgement of a competent electrical engineer or the requirements of the licensing authority. Standards are cited for guidance; always work from the current licensed text.